In the 2010 ADA and the 2012 TAS there are certain elements that require front approach and parallel approach. But not all of those also require for them to be centered along the element. This newsletter will enumerate the one’s that do. Other elements such as lavatories and sinks and operating mechanisms only require forward approach but it is not required to be centered.

Centered Elements

602 Drinking Fountain
602.2 Clear Floor Space. Units shall have a clear floor or ground space complying with 305 positioned for a forward approach and centered on the unit. Knee and toe clearance complying with 306 shall be provided.

0415162e-1488-4473-9b92-a237f3a6f1b8

611 Washer and Dryer
611.2 Clear Floor Space. A clear floor or ground space complying with 305 positioned for parallel approach shall be provided. The clear floor or ground space shall be centered on the appliance.

6b13ba6b-b466-4375-a510-dc9238e760d9

703 Signage
703.4.2 Location. Where a tactile sign is provided at a door, the sign shall be located alongside the door at the latch side. Where a tactile sign is provided at double doors with one active leaf, the sign shall be located on the inactive leaf. Where a tactile sign is provided at double doors with two active leafs, the sign shall be located to the right of the right hand door. Where there is no wall space at the latch side of a single door or at the right side of double doors, signs shall be located on the nearest adjacent wall. Signs containing tactile characters shall be located so that a clear floor space of 18 inches (455 mm) minimum by 18 inches (455 mm) minimum, centered on the tactile characters, is provided beyond the arc of any door swing between the closed position and 45 degree open position.

f6d760d0-7f9a-4a36-88c7-02f962ba5d06

d3894b43-1abc-43e3-91c2-0727a5ace229

This sign has a drinking fountain in front of it, therefore the requirement for a clear floor space centered on the sign has not been met.

804.3 Kitchen Work Surface (Residential only)
804.3.1 Clear Floor or Ground Space. A clear floor space complying with 305 positioned for a forward approach shall be provided. The clear floor or ground space shall be centered on the kitchen work surface and shall provide knee and toe clearance complying with 306.

 

207edc3c-87a6-41a5-a996-3ddda3de02f7

904.4 Sales and Service Counters.
EXCEPTION: In alterations, when the provision of a counter complying with 904.4 would result in a reduction of the number of existing counters at work stations or a reduction of the number of existing mail boxes, the counter shall be permitted to have a portion which is 24 inches (610 mm) long minimum complying with 904.4.1 provided that the required clear floor or ground space is centered on the accessible length of the counter.

6b522a5c-dc11-415b-a08d-19179502a6e7

Playground Transfer Systems
1008.3.1.3 Transfer Space. A transfer space complying with 305.2 and 305.3 shall be provided adjacent to the transfer platform. The 48 inch (1220 mm) long minimum dimension of the transfer space shall be centered on and parallel to the 24 inch (610 mm) long minimum side of the transfer platform. The side of the transfer platform serving the transfer space shall be unobstructed.

bcba7ea3-71f9-439c-9f5e-38a00612982d

7a16ad3d-803c-4a9f-9766-b70fe1323492

Pool Transfer Walls
1009.4.1 Clear Deck Space. A clear deck space of 60 inches (1525 mm) minimum by 60 inches (1525 mm) minimum with a slope not steeper than 1:48 shall be provided at the base of the transfer wall. Where one grab bar is provided, the clear deck space shall be centered on the grab bar. Where two grab bars are provided, the clear deck space shall be centered on the clearance between the grab bars.

55a1a89b-a967-464d-8650-03109d6cc185

1009.4.3 Wall Depth and Length. The depth of the transfer wall shall be 12 inches (305 mm) minimum and 16 inches (405 mm) maximum. The length of the transfer wall shall be 60 inches (1525 mm) minimum and shall be centered on the clear deck space.

f0a7b5ee-3207-49d2-9026-bdb5d1d415d9

1009.5.2 Transfer Space. A transfer space of 60 inches (1525 mm) minimum by 60 inches (1525 mm) minimum with a slope not steeper than 1:48 shall be provided at the base of the transfer platform surface and shall be centered along a 24 inch (610 mm) minimum side of the transfer platform. The side of the transfer platform serving the transfer space shall be unobstructed.

965997d7-1ace-4ec7-963b-bfd85782bfea

Forward Approach but not centered

The following elements are required to have a forward approach, but do not require it to be centered.

605 Urinals

1a7018eb-cad8-456b-9af1-4088c8613114

606 Lavatories and Sinks

76dc07be-614e-42bf-a30f-19b3b6eecea1

902 Dining and Work Surfaces

64bb8740-069d-48f2-839f-a45220405f08

Parallel Approach bu not centered

The following elements are allowed to have a parallel approach, but do not require it to be centered.

704 Telephones

9e1c588b-b857-4b61-accb-abc95ff762e3

804 Range or cooktop

c1fbcf14-3cfa-43f3-b250-ccd4fe31ff39

Photo: The range can have a parallel approach, but the sink requires a forward approach.

904 Sales Counters

If parallel approach is provided, it requires 36″ in width and 36″ in height plus the same depth as the main counter

4bee034e-0943-4920-bd44-e6d8cd8c3cd1

Photo 1: This photo is of a service counter/reception desk at a hotel that did not provide the 36″ wide x 36″ high counter

If forward approach is provided, it requires 30″ in width and 36″ in height, plus the same depth as the main counter and a knee and toe space per 306

125c4091-63a0-49a7-9e34-a38602c4cab7

Photo 2: This counter has provided a lower portion that meets the requirements for the parallel approach. (photo provided by Structures and Interiors)

602 Exception at Drinking Fountains for children

5bf7f0d4-d47d-4eeb-a4c4-3deceba67272

606 Exception at sinks in kitchens without a cooktop or range

104c13ed-a959-44ee-b462-811e03f7520b

Photo: This kitchen has a built in microwave but NO cooktop, therefore it can take the exception for parallel approach at the sink.

606 Exception at Wet bars

510e58b8-f96d-43be-96df-d725b85b5957

606 Exception at lavatories or sinks for children under 5

f2fc8d0f-8453-481a-b3d8-7711dd8c498a

804 Freezers or Refrigerator in kitchens

2600a6fe-d8ae-471c-8a71-a94aa62dca7a

Continuing Education Opportunities

November 2- International Facilities Managers Association Convention in San Antonio, Texas

November 7- provided by SSTL Codes 4 hr ADA seminar in Tulsa OK

If you want to learn more about the new Standards, The ADA Companion Guide explains the 2004 ADAAG Guidelines  with commentary and explanations throughout.  The 2004 Guidelines were adopted by the DOJ to create the 2010 Standards and by Texas to create the 2012 TAS.  This book explains the technical requirements for both.

NOTE: Our offices will be closed October 1 and 2nd and again October 8th and 9th for religious observance.
 If you have any questions about these or any other topics, please feel free to contact me anytime.
Marcela Abadi Rhoads, RAS #240